RAMO 30 E, M12, round collar, illuminated, 2 NC, Gold, M12 8-pin A-coded, reset by rotating, Mushroom head red, arrows red, illuminable

Description

Emergency stop with M12 connection: RAMO E switches are designed with two NC contacts for a switching voltage of 35 V. They comply with all applicable ISO and IEC standards and are characterized by their simple, time-saving installation. Like the entire RAMO series, the emergency stop switches feature installation-friendly M12 plug-in connections that reduce wiring effort to a minimum.

Additional information according to UL certificate:
For Class 2 Power Source or Limited Voltage / Limited Current only
Installation only by trained specialist personnel.
Type 4x Indoor only with cable "Cat. No. 7000-08061-0210100 PUR 4x0.25mm² with M8 connector, rated max. 30VAC/DC 4A, manufactured by Murrelektronik GmbH" and "Cat. No. 7000-12221-0340100 PUR 4x0.34mm² with M12 connector, rated max. 30VAC/DC 4A, manufactured by Murrelektronik GmbH"
For Use on a Flat Surface of a Type 1 or 4x indoor only Enclosure.

 

technical data

general

Potential free yes
Color of mushroom red
Legending color red
Collar color yellow
Luminous element color red
Collar shape round
Operating temperature, min. -40 °C
Operating temperature, max. 85 °C
Storage temperature, min. -40 °C
Storage temperature, max. 90 °C
illuminated Yes
Packaging Box
Packaging unit 2 pcs.
Net weight 32.6 g
Operating life 50,000 cycles
B10 65,000 cycles
B10d 130,000 cycles
Degree of protection, front side, according to DIN EN 60529 IP65
IP66
Degree of protection, rear side, according to DIN EN 60529 IP65
IP67
Environment resistance IEC 60068-2-14
IEC 60068-2-30
IEC 60068-2-33
IEC 60068-2-78
Shock resistance according to standard IEC 60068-2-27 50 g at 11 ms amplitude semi-sinusoidal
Salt-spray resistance according to standard IEC 60068-2-11
Impact resistance IK 06 side
07 frontal
Oscillation restistance according to standard IEC 60068-2-6 5 g at 10...500 Hz
Minimum order quantity (MOQ) 2 pcs.
Pollution degree acc. to DIN EN 61010-1 Pollution degree 2
RoHS compliant Yes
REACH compliant Yes
Country of origin HU

mounting diameters

Outside dimension, length 34.5 mm
Outside dimension, width 34.5 mm
Outside dimension, height 69.9 mm
Mounting hole 30.3 mm
Mounting depth 36.3 mm
Installation height 33.6 mm
Grid, min. 35 mm

mechanical data

Terminal on the rear M12 8-pin A-coded
Fixing Threaded ring
Actuation function latching
Threaded ring torque, max. 1.2 Nm
Resistance to force on the side 300 N
Contact function 2 NC
Contact material Gold
PIN 1 Normally closed contact 1
PIN 2 Normally closed contact 2
PIN 3 GND
PIN 4 Normally closed contact 1
PIN 5 Normally closed contact 2
PIN 6 LED +
Resetting by rotating

electrical data

Rated insulation voltage 250 V
Rated surge voltage 2,500 V
Operating voltage of the luminous element, min. 19.2 V
Operating voltage of the luminous element, max. 28.8 V
Rated voltage, min. 1 V
Rated voltage, max. 35 V
Voltage type DC
Rated operating current 0.1 A
Rated operating voltage 1-35 V
Operating current of the luminous element, min. 16 mA
Operating current of the luminous element, max. 24 mA
Rated current, min. 0.001 A
Rated current, max. 0.1 A
Power loss 0.00080 W
Overvoltage category 2
Kind of short circuit protective device fuse 250 V / 0,1 A / 1,5 kA gG quick
Conditional short circuit current 1,000 A

Specifications according to IEC 60947-5-1

Rated operating voltage 35 V (AC-15)
35 V (DC-13)
Rated surge voltage 2,500 V

Specifications according to UL 60947

UL Enclosure Type Rating front side type 4X indoor

direct links

drawings

Dimensioned drawing

Mounting hole drawing

Schematic diagram